Door Label |
Mounting | Wall Construction |
Max. Width |
Max. Height |
Max. Area |
Certifying Agency |
|||
---|---|---|---|---|---|---|---|---|---|
4 Hr Label | Face of Wall and Between the Jambs* | Masonry/Steel | 13'6" | 13'-6" | 152 Sq. Ft. | UL | |||
4 Hr Label | Face of Wall and Between the Jambs* | Masonry/Steel | 12' | 10' | 120 Sq. Ft. | FM | |||
Oversize 4 Hr |
Face of Wall and Between the Jambs* | Masonry/Steel | 41'2" | 25'4" | 683 Sq. Ft. | UL | |||
Oversize 4 Hr |
Face of Wall and Between the Jambs* | Masonry/Steel | 18' | 18' | 324 Sq. Ft. | FM | |||
3 Hr | Face of Wall and Between the Jambs* | Non-Masonry | 12' | 12' | 144 Sq. Ft. | UL | |||
1 1/2 Hr | Face of Wall and Between the Jambs* | Non-Masonry | 12' | 10' | 117 Sq. Ft. | FM | |||
Oversize 3 Hr |
Face of Wall and Between the Jambs* | Non-Masonry | 14' | 12' | 168 Sq. Ft. | UL | |||
Oversize 1 1/2 Hr |
Face of Wall | Non-Masonry | 14' | 11' | 140 Sq. Ft. | FM | |||
Oversize 3 Hr |
Face of Wall and Between the Jambs* | Steel Tube Inside Non-Masonry |
16' | 14' | 224 Sq. Ft. | UL | |||
Oversize 1 1/2 Hr |
Face of Wall | Steel Tube Inside Non-Masonry |
14' | 11' | 140 Sq. Ft. | FM | |||
3 Hr | Face of Wall | Steel Tube Inside Non-Masonry |
12' | 12' | 144 Sq. Ft. | UL | |||
3 Hr | Face of Wall | Steel Tube on Masonry or Non-Masonry |
12' | 10' | 120 Sq. Ft. | FM | |||
Oversize 3 Hr |
Face of Wall | Steel Tube on Masonry or Non-Masonry |
24' | 24' | 576 Sq. Ft. | UL | |||
Oversize 3 Hr |
Face of Wall | Steel Tube on Masonry or Non-Masonry |
18' | 18' | 324 Sq. Ft. | FM | |||
* Between jambs doors are based on width of wall and from floor to top of coil (under lintel). Factory Mutual (FM) reviews each size above the over size service on a case-by-case basis |
Application - Exterior/Interior for fire rated walls
Operation - Non-motorized, mechanical floor resettable hoist with viscous governor
Mounting - Face of wall (between jambs optional)
Drop Speed - Meets NFPA 80 requirements of 6" to 24" per second
Models
Material - Steel slats in a variety of gauges
Finish - Baked-on polyester top coat in Gray, Tan, White, or Brown
Guides - Three steel angles (some use structural and some are roll formed)
Bottom Bar - Steel double angle
Counterbalance - High tensile helical torsion spring housed in a steel tube or pipe
Brackets - Steel plates to support counterbalance, curtain, and hood
2-year material and workmanship 1-year labor
Fire Sentinal® |
Time-delay release device |
Available in 1-1/2 hr, 3 hr, and 4 hr labels | |
Smoke Detectors Heat Detectors |
Photoelectric or ionization-type smoke detectors. Heat detectors are also available. |
UL-listed brush-type smoke seals (“S” label) to satisfy smoke retardation requirements of certain applications. | |
A Factory Mutual (FM) requirement. | |
FM labels are available in 1-1/2 hr, 3 hr, and oversized door. | |
Horns and horns with strobes are available. | |
To satisfy a variety of applications. See page 10 for more detailed information. |
Downloadable Brochure and Warranty |
|
|
|
Brochure | Warranty |